Before the First Christmas Booking: Five Airflow Checks for UK Licensed Premises
There is a particular fortnight in December when a venue that seats eighty people comfortably starts holding a hundred and forty, standing, in coats, with the doors opening every ninety seconds. Nothing about the building has changed. Everything about the load has.
Most winter maintenance schedules are written around frost protection and boiler checks. Few of them are written around the fact that the busiest trading period of the year is also the period when extract systems are least efficient, doors are most often propped open, and filters are at their dirtiest. The following five checks are intended to be done in late November, before the bookings arrive.
1. Front-of-house carbon dioxide under real load
A CO2 reading taken in an empty bar at eleven in the morning tells you almost nothing. What matters is the reading at 21:30 on a Friday with the room at capacity.
Place a portable monitor in the breathing zone, away from the entrance lobby and clear of the supply grilles, and log it for a full trading session. A well-ventilated front-of-house area under crowd load should generally stay below around 1,000 to 1,500 ppm for most of the evening, with the higher end tolerable briefly at peak. Sustained readings well above that indicate that the room is being occupied faster than it is being flushed, which is a make-up air problem as often as it is an extract problem.
This is also the check most likely to be quoted back at you. Keep the log.
2. Cellar extract and the air change nobody notices
Cellars are cool, quiet and rarely inspected during service, which is precisely why their ventilation fails unnoticed. Beer lines, yeast activity and the simple fact of a sealed room below ground mean that a cellar without adequate extract will become humid, and humidity is unkind to kegs, stock and electrical equipment alike.
Check that the extract fan is running and not merely humming, confirm the grilles are clear of cardboard and empty crates, and verify that the make-up path into the cellar is open rather than blocked by a stack of deliveries. Where a cellar cooling unit is fitted, check that its condensate is draining and that the coil is not matted with dust.
3. Toilets and the extract that was quietly switched off
Sanitary accommodation extract is one of the most commonly disabled systems in licensed premises, usually because a fan became noisy, or because someone decided it was drawing cold air across the room in January. The result is a room that relies on an open window and goodwill.
Confirm every toilet and washroom extract terminal is drawing air, using a smoke pencil or a handheld anemometer rather than a hand held up hopefully in the doorway. Check the transfer path, whether that is a door grille or an undercut, and check it has not been sealed during a refurbishment.
4. Make-up air under crowd load
A commercial kitchen extract cannot remove air that the building will not let in. Once the canopy is running at full rate and the front doors are open to a queue, the venue is in a contest between the extract fan and the door closer. The symptom is familiar: the canopy loses its capture, cooking odours migrate into the bar, and the extract fan sounds laboured without appearing to do anything.
As a working principle, kitchen extract should be matched by purpose-provided make-up air at roughly 80 to 90 per cent of the extract volume, with the balance coming from the general building. Check that make-up air units, louvres and transfer grilles are unobstructed, that any heated make-up supply is actually operating, and that no recent building work has closed off the path the designer assumed.
5. Filters, belts and the maintenance record
Before the rush, look at the filters rather than the schedule that says they were changed. A filter that has gone grey and soft is no longer performing to the grade printed on its frame, and the fan is paying for it in pressure. Check belt tension and condition on any belt-driven unit, confirm that variable speed drives are at the intended setting rather than the setting someone found convenient, and note the pressure drop across each filter bank so there is a baseline to compare against in January.
This is also the moment to assemble the paperwork. A folder containing the ventilation schedule, the last service report, the filter grades fitted, the commissioned extract rates for the canopy and toilets, and the CO2 logs from a busy session is worth far more during a complaint than a hurried phone call afterwards. Environmental health officers and insurers tend to ask for evidence of management, not evidence of perfection.
Assembling the file before you need it
None of these checks is complicated, and none of them requires a shutdown. What they require is a couple of hours in a quiet week, a working anemometer or smoke pencil, and a decision about who is responsible for each item.
December will bring the crowds regardless. The venue that has walked its airflow paths in November will spend the busy weeks serving, rather than explaining.