Before the Heating Goes On: A 2026 Ventilation Audit for UK Commercial Premises
Photo: ajay_suresh, CC BY 2.0, via Wikimedia Commons
The shift from cooling to heating is a useful moment for UK commercial premises. Windows close, occupancy patterns change and ventilation systems that performed adequately in milder weather can begin to show their weaknesses. For facilities managers, the temptation is to treat the pre-winter walkthrough as a box-ticking exercise: glance at the plant room, confirm the heating is running and move on. That approach is increasingly difficult to defend. A more structured audit, carried out room by room and recorded properly, gives both operational confidence and a clearer compliance trail under Building Regulations Part F and HSE expectations.
Start with the asset list, not the plant room
A ventilation audit should begin with the design intent. Identify the air handling units, mechanical ventilation with heat recovery units, extract fans, local exhaust ventilation, CO2 monitors and associated controls that serve each zone. Confirm which areas are naturally ventilated and which rely on mechanical supply or extract. This matters because a fault in one air handling unit can affect several rooms, while a blocked extract grille in a single toilet or kitchen may be invisible from the plant room.
The asset list should also record the responsible person, maintenance regime and any known defects. Approved Document F, Volume 2, sets out the non-domestic ventilation provisions for England, and the devolved administrations have equivalent requirements. The audit is not a substitute for design or commissioning documentation, but it should connect the installed system to the building's current use. Where occupancy or fit-out has changed since commissioning, that change needs to be noted.
CO2 sensors: verify calibration and placement
Demand-controlled ventilation is only as good as the sensor feeding it. Many CO2 sensors use non-dispersive infrared technology, which can drift over time. A sensor that reads low will under-ventilate a meeting room; one that reads high will waste energy. Before winter, compare sensor readings with a calibrated reference instrument and check the calibration date against the manufacturer's schedule.
Placement matters as much as calibration. Sensors should represent the occupied zone, not a dead corner, a sunlit surface or the immediate path of a supply diffuser. Record the location, the reading, the reference reading and any adjustment made. If calibration cannot be verified, the control strategy should fall back to a safe fixed ventilation rate rather than trusting an unreliable signal. This is exactly the kind of detail that makes a compliance record useful later.
Filters, fans and heat exchangers
Filter condition is the simplest indicator of whether a system is being maintained. Check differential pressure readings where gauges are fitted, inspect filter media and replace according to the manufacturer's specification rather than waiting for visible dust. Record part numbers and pressure readings so that trends can be reviewed.
Fans, belts, bearings and dampers should be checked for unusual noise, vibration, overheating or seizure. On heat recovery units, inspect the exchanger for fouling and confirm that condensate drains are clear and trapped correctly. Frost protection must be operational before the first cold spell. A unit that trips out on frost protection in January may leave occupied spaces under-ventilated for days.
Ductwork: look for leakage and unintended paths
Ductwork leaks waste energy and can undermine balanced ventilation. Inspect accessible joints, access panels, flexible connections and seals. Look for displaced gaskets, damaged insulation and gaps around penetrations. Where there is reason to suspect significant leakage, targeted testing or smoke testing may be justified.
Also check the external environment. Outdoor air intakes should be clear of flues, loading bays, refuse areas and vehicle exhaust. Extract discharges should not be recirculating into intakes or opening windows. These are not abstract design issues; they are common causes of odour and air quality complaints in mixed-use and light industrial premises.
Room-by-room checks in occupied and wet areas
The audit should include the spaces people actually use. In offices and meeting rooms, check CO2 readings, temperature, humidity, odours and stuffiness. In toilets, kitchens and tea points, confirm that extract runs when required and that make-up air can reach the extract point. Door undercuts, transfer grilles and trickle vents are part of the ventilation path, not decorative details.
In commercial kitchens, canopy extract and make-up air need particular attention. In workshops and process areas, local exhaust ventilation may fall under COSHH controls, and HSE expects employers to ensure workplaces are adequately ventilated. The audit should record the activity, occupancy and observed conditions, not just the equipment status.
Controls and seasonal changeover
Controls are often where good intentions fail. Check time schedules, setpoints, CO2 demand-control settings, economiser operation and frost protection. Confirm that no one has disabled a ventilation strategy to save energy or because a sensor was nuisance-triggering. Review BMS alarms and trends where available. A short trend review can reveal whether a system is running outside its intended hours or failing to respond to occupancy.
Build the compliance record
The audit becomes defensible when it is documented. Record the date, the competent person, the instruments used and their calibration status, the readings taken, the actions required and the owner of each action. Link the record to maintenance schedules, commissioning data and any permits to work. Part F and HSE guidance do not demand a single prescribed form, but they do expect evidence of adequate ventilation, maintenance and review. A clear audit trail is more persuasive than a folder of unsorted service sheets.
Close out actions before the heating season is fully established, then recheck after the first cold snap. Ventilation is a seasonal service, not a one-off inspection. The facilities managers who get this right will spend less time reacting to winter stuffiness complaints and more time demonstrating that the building has been managed with competence and care.