At Rack Level: Ventilation Evidence for UK Warehouses and Fulfilment Centres

Airflow Services
At Rack Level: Ventilation Evidence for UK Warehouses and Fulfilment Centres

UK warehouses and fulfilment centres are rarely simple boxes. They combine tall storage volumes, mezzanine offices, packing lines, goods-in areas and rapidly changing occupancy. Ventilation plant is often mounted at roof level, and the resulting readings can suggest that a building is well served when the air at working height tells a different story. The question is not whether the roof extract fans are running. It is whether the air in the zones where people spend their shifts is being supplied, moved and removed as intended.

Why height changes the ventilation question

In a tall single-volume building, air does not behave as a uniform mixture. Thermal stratification can produce warmer, more buoyant air at high level and cooler air near the floor. In winter, heating and solar gains through roof lights can strengthen that gradient. In summer, warm roof surfaces and high-level plant can have a similar effect. The result is a vertical profile in which temperature, humidity and contaminant concentrations differ between the roof void and the racking face.

That matters because many warehouse ventilation strategies are designed around heat removal at high level. Roof-mounted extract is effective for clearing warm air that has risen, but it does not automatically capture dust, packaging odours, forklift emissions or other low-level contaminants close to the breathing zone. A high-level CO2 sensor may report a reassuring figure while a packing bench or mezzanine office has poorer air movement. The building is not necessarily under-ventilated everywhere. It may simply be ventilated unevenly, with evidence collected at the wrong height.

The occupied zone is the unit of evidence

A useful airflow survey starts by defining the occupied zones rather than the plant schedule. In a fulfilment centre these might include pick faces at multiple rack levels, packing benches, goods-in and dispatch areas, mezzanine offices, welfare rooms and battery charging areas. Each zone has its own height, activity level, local extract, supply diffusers and occupancy pattern.

Record the breathing height that applies. For seated office work on a mezzanine this may be around 1.1 metres; for standing work at a packing bench or rack face it may be around 1.5 metres. Note whether the zone is open to the main warehouse volume or separated by partitions, and whether doors are normally open or closed. A mezzanine office with a door to the warehouse is not the same ventilation zone as an enclosed room with its own supply and extract.

Reading the vertical profile

Evidence should compare conditions at high level with conditions in the occupied zone. Where possible, take simultaneous readings using calibrated instruments, or take sequential readings under stable conditions with the same plant state and door positions. Carbon dioxide remains a useful occupancy tracer in densely occupied areas, but it must be interpreted alongside temperature, relative humidity and, where relevant, carbon monoxide, nitrogen dioxide, VOCs or dust.

A vertical comparison can reveal whether the building is mixing air effectively or whether stratification is separating the occupied zone from the extract point. If high-level extract is removing air that has already passed through the occupied zone, the profile may look consistent. If make-up air is entering low and rising quickly to roof level, it may bypass the rack faces and packing benches. The readings should be recorded with the time, height, activity and plant condition so that the pattern can be reviewed rather than treated as a single spot check.

Make-up air follows the path of least resistance

Extract cannot work without make-up air, and in warehouses the make-up path is often uncontrolled. Loading bay doors, roller shutters, louvres, personal doors and fabric leakage all admit air. Wind pressure and temperature differences affect how much enters and where it goes. A roof extract system may be pulling air from the nearest opening rather than drawing it through the occupied zone.

Survey the make-up air paths as part of the evidence file. Note which doors are open during shifts, whether louvres are clear, and whether pressure differences cause doors to be difficult to open or to stand open. Check that intended make-up air louvres are commissioned and unobstructed. Where smoke or pressure testing is used, record the method and the observed direction of airflow. The aim is not to prove that a path exists in theory, but to show which path the building uses in practice.

Extract points and the illusion of service

A roof-mounted unit can be running, balanced and maintained while contributing little to air quality at rack level. The evidence file should confirm the location and measured airflow of extract grilles, not only the status of the roof plant. High-level extract may be appropriate for heat, but low-level contaminants may need local capture or a different extract arrangement. Packing areas, battery charging and goods-in zones deserve particular attention because they can generate contaminants close to where people work.

If destratification fans are fitted, record their operation and effect. Mixing can reduce temperature gradients and improve uniformity, but it can also distribute contaminants more widely if the source is not controlled. The point is to record what the building is doing, not to assume that any additional fan improves the ventilation outcome.

A practical evidence approach

A proportionate survey for a UK warehouse or fulfilment centre can be built around five steps: define the occupied zones on a floor plan; place instruments at breathing height and at high level for comparison; record plant state, door positions and activity during each reading; survey make-up air paths and extract grilles; and photograph the relevant locations with notes on height and distance. The output should be a clear record of conditions in the occupied zones over a representative period, together with the limitations of the survey.

That record supports sensible action. It may point to repositioning sensors, adjusting make-up air, adding local extract at a packing line, rebalancing grilles or reviewing the use of high-level extract during occupied hours. It also prevents a common overclaim: that because the roof units are serviceable, the building has been proven to ventilate the places where people work.

Airflow Services treats the occupied zone as the starting point for ventilation evidence in commercial premises. In warehouses and fulfilment centres, the height of the work is part of the problem, and the evidence should follow it.

All Articles

Related Articles

When the Building Is Asleep: Establishing an Overnight Airflow Baseline for UK Commercial Premises

When the Building Is Asleep: Establishing an Overnight Airflow Baseline for UK Commercial Premises

The Sensor Is Not the System: Proving Basement Car Park Ventilation in UK Commercial Buildings

The Sensor Is Not the System: Proving Basement Car Park Ventilation in UK Commercial Buildings

From Setting to Proof: Commissioning Intermittent Extract Controls in UK Premises

From Setting to Proof: Commissioning Intermittent Extract Controls in UK Premises