When the Building Is Asleep: Establishing an Overnight Airflow Baseline for UK Commercial Premises
A ventilation survey carried out between nine and five measures a system with an audience. Doors stand open, kitchen and sanitary extract runs on demand, staff generate heat and carbon dioxide, and the building management system behaves as it does when it believes the building is busy. Those readings are genuine, but they describe a system in one particular state rather than the system itself.
Remove the occupants and a different set of behaviours becomes visible. Plant that should have stopped at 19:00 but did not. A damper that has never once closed. Outdoor air entering through a façade that looks sealed. A carbon dioxide baseline that will not fall overnight, hinting at a source or pathway that daytime data could never separate from the crowd.
Why occupied hours conceal the underlying system
During occupation, the ventilation strategy and the building's users are effectively working in parallel. People propped doors, openable windows left ajar through the afternoon, local extract in a tea point, photocopiers and IT racks adding load, and the controls overriding schedules because a sensor reports activity. Every one of these introduces airflow that the design did not necessarily intend and the survey cannot easily attribute.
The consequence is that a daytime survey tends to confirm that air is moving, not that the system is doing what the schedule and the design say it should. For compliance purposes that distinction matters. Approved Document F and the commissioning guidance that supports it are concerned with the provision of adequate ventilation in the states the building will actually experience, including the unoccupied ones. An assessment that only ever sees the building at full tilt leaves a substantial part of that obligation unexamined.
What an empty building reveals that a busy one cannot
A quiet building isolates the mechanical system from its occupants, and four categories of finding tend to emerge.
Scheduling faults. Time clocks and BMS calendars drift, particularly after the autumn clock change, when summer-time settings can persist for weeks. A November monitoring period is a good moment to catch this: plant starting an hour late, overrun timers left at commissioning values, or weekend schedules applied to a building that now operates six days a week.
Fan and damper standby behaviour. When a supply or extract fan is commanded off, is it actually off? Variable speed drives in standby, dampers that fail to the open position, and control valves that leak past their seat all show up clearly when there is no occupancy load to mask them. So does the opposite fault: a system that runs continuously because nobody has ever interrogated the schedule, quietly consuming energy and over-ventilating a space that does not need it.
Unintended infiltration. With mechanical plant at rest, the building's pressure regime is governed by weather, stack effect and the relative balance of whatever extract remains live. Differential pressure readings taken across the façade during a still night, and again during a windy one, give an indication of envelope performance that is very difficult to obtain at midday.
Baseline carbon dioxide and background concentrations. In a genuinely unoccupied space overnight, CO2 should decay towards outdoor levels. When it settles well above them, the explanation is usually one of three: a slow decay from a poorly ventilated volume with no night purge, an internal source such as a gas appliance or stored materials, or a pathway connecting the space to another occupied or process area.
Designing a defensible monitoring window
An overnight baseline is only evidence if the conditions are recorded alongside the readings. A workable routine for most commercial premises looks like this.
Agree access and isolation with the occupier and the security provider in advance, and record in writing what state the building will be in: plant left on schedule, no cleaning contractors, no deliveries, all external doors closed and alarmed. Where cleaning or security patrols must continue, log their timings, because a door opened at 02:30 will appear in the pressure data and needs an explanation.
Choose a window of at least three consecutive nights, ideally spanning a weekday and a weekend, so that weekday and weekend schedules are both captured. Note the weather for each night, including external temperature, wind speed and direction; the nearest reliable observation is sufficient, provided it is cited.
What to log, and at what resolution
Five-minute intervals are adequate for most parameters, though duct pressure and fan status benefit from one-minute logging where the controls permit it. The minimum set is carbon dioxide, air temperature and relative humidity in two or three representative zones; differential pressure across the envelope and across key duct sections; fan run status, speed and damper position from the BMS trend log; electrical sub-metering for the ventilation plant; and door contact events on external openings.
Instrument calibration certificates should be current, and any sensor that will inform a conclusion should be cross-checked against a reference before the window opens. Where a BMS trend is the only source, export the raw log rather than a summary graphic; summaries lose the very detail that makes overnight data useful.
Interpreting the baseline honestly
Analysis should begin with a simple question: does the observed behaviour match the intended schedule, and where it does not, is the deviation mechanical, controls-related or driven by the envelope? Plot the night as a timeline rather than a set of averages. Averages smooth away the transitions that carry the diagnostic value.
Carbon dioxide decay curves can be used to estimate effective air change in the unoccupied space, but the estimate should carry its assumptions with it: volume, occupancy history before the window, and whether mixing can reasonably be assumed. Pressure differentials should be read alongside wind data; a single negative reading on a gusty night proves little.
Making the baseline part of the ventilation record
The output is a short annexure to the existing ventilation file: purpose, dates, building state, instrumentation and calibration, weather, raw and processed data, findings, remedial actions and a re-test date. It sits naturally beside commissioning records and any airtightness testing carried out to CIBSE TM23, and it gives future surveys something to compare against.
Buildings change. A tenant fit-out, a new extraction system or a change of use can alter the airflow regime without anyone revisiting the original design intent. An overnight baseline taken before and after such a change is one of the cheapest forms of assurance available, and it answers a question that no daytime survey can: what does this building do when nobody is asking anything of it?