When the Number Looks Fine: CO2 Monitoring and the Discipline of Ventilation
Photo: Mice of Mu, CC BY-SA 4.0, via Wikimedia Commons
CO2 monitoring has become a familiar sight in UK offices and school buildings. In 2026, many reception areas, classrooms and meeting rooms carry a small display showing parts per million, sometimes with a green, amber or red indicator. The temptation is to treat a green number as proof that a room is well ventilated. That is a category error. A monitor measures concentration at one point; a ventilation plan determines how air moves, who checks it, and what happens when conditions change.
The reassurance trap
A visible reading can create a false sense of closure. Facilities teams may point to the display during a walkround; teachers may glance at it between lessons; office managers may assume the building management system is handling the rest. Yet a single CO2 figure says nothing about distribution, maintenance or response. A room can show an acceptable average while one corner remains stagnant. A sensor can read low because it is mounted near a door, or high because it sits beside a group of occupants. Without a protocol, monitoring becomes decoration with a number attached.
Placement is part of the measurement
Sensor location should be chosen for the breathing zone, not for convenience. In classrooms, that generally means around seated head height, away from windows, doors, direct sunlight, radiators and supply diffusers. In open-plan offices, monitors should represent occupied zones rather than the reception desk or the IT comms cupboard. Avoid placing units where they can be covered, knocked or exposed to cleaning sprays. If a monitor is moved, note the change and treat earlier readings as a separate dataset. A measurement without a location is difficult to defend.
Calibration and ownership
Most commercial CO2 monitors use non-dispersive infrared sensors. Some rely on automatic baseline correction, which assumes the space will periodically fall to outdoor levels. In continuously occupied buildings, that assumption can be weak. Calibration intervals should follow the manufacturer’s instructions, and the results should be recorded in the maintenance file. More important is ownership. A named person, or a named role, should be responsible for checking the device, replacing filters where fitted, reviewing trends and escalating faults. A monitor with no owner is furniture. In a school, that role may sit with the premises manager; in an office, with the facilities coordinator. The point is not the job title but the handover.
Thresholds should trigger tasks
A number becomes useful only when it is tied to an action. UK guidance commonly uses 1,500 ppm as an upper action level in schools, with lower values indicating a need to review ventilation. Offices may work to a tighter band. Rather than debating a single ideal figure, set a tiered response: a sustained reading above 1,000 ppm prompts a check of dampers, windows, doors and occupancy; a reading approaching 1,500 ppm triggers immediate remedial action, such as increasing mechanical ventilation or reducing occupancy; repeated excursions require a maintenance investigation. Record the action taken and the time. This turns a dashboard into a decision log.
From dashboard to decision log
The practical output of monitoring should be a short daily or weekly review, not a live graph nobody checks. In schools, a ventilation champion can note readings at set times and confirm that windows or vents are being used as intended. In offices, the building manager can compare CO2 trends with meeting-room bookings and HVAC schedules. If a room consistently underperforms, the question is not merely 'what was the reading?' but 'what changed?' Filters, belts, actuators, dampers and sensors all drift. Monitoring should feed the maintenance system, not sit outside it.
A workable protocol
A sensible 2026 protocol has four parts: a placement plan, a calibration and maintenance schedule, a tiered action threshold, and a named owner. Add a simple escalation route for faults and a periodic review of the data against occupancy. None of this replaces design, commissioning or adequate outdoor air. It simply makes monitoring honest. The CO2 display is a useful instrument, but it is not a ventilation plan. The plan is the set of decisions that determines what happens when the number moves.