The Box on the Wall: Why Sensor Placement Decides Whether IAQ Data Is Evidence

Airflow Services
The Box on the Wall: Why Sensor Placement Decides Whether IAQ Data Is Evidence

Walk into almost any recently refurbished commercial building and you will find a monitor on a wall. It glows. It has an app. It may even have a colour-coded dial. And fairly often, the people sitting nearest to it will tell you it is wrong.

They are usually right, and so is the monitor. The disagreement is rarely a fault in the electronics. It is almost always a question of geography.

Two readings, one room

A CO2 sensor mounted beside a reception desk and another mounted at the far end of the same open-plan floor can differ by 400 ppm or more without either being defective. One sits in the return air path of a supply diffuser; the other sits in a pocket of still air behind a partition. Neither point is the room. Both are points in the room.

This is the first thing to accept before spending money on better hardware: a monitor reports the air at its own inlet, not the air in the space. Air quality is not uniform, and the figures that reach a dashboard are a sample, not a verdict.

The breathing zone is not the ceiling void

Placement guidance is broadly consistent across manufacturers and test standards, and it is routinely ignored because the wall by the door is convenient and the ceiling grid is already there.

A defensible position sits roughly 1.1 to 1.7 metres above floor level, representing the zone occupied by seated and standing people. It should be clear of supply diffusers, away from doors and openable windows, out of direct sunlight, and not directly above radiators, printers, or vending machines. It should not be tucked into a corner where the air is stagnant, nor fixed to a partition that will be moved within a fortnight.

Ceiling-mounted units have their place, particularly where ducted sampling is used, but a CO2 reading taken at 2.8 metres tells you about the stratified layer near the slab, not about the person at the desk.

Interference: kitchens, roads and the building's own habits

Particulate sensors are the most frequently misread instruments on site, largely because they are indiscriminate. An optical PM2.5 sensor will happily count frying aerosol, candle smoke, toaster fumes and the emissions of a delivery van idling outside the loading bay. A unit mounted outside a kitchen door will report the kitchen all day and be blamed for the restaurant.

Volatile organic compound sensors are worse. Most are not selective, and they respond to cleaning products, new furniture, hand sanitiser and the perfumes of a busy reception. A VOC spike is a prompt to investigate, not a finding in itself.

Interference is not limited to the building. Premises on a busy A-road will show a particulate baseline that has far more to do with the traffic outside than with the filtration inside. That is not a reason to discard the data, but it is a reason to interpret it alongside the windows, the doors and the time of day.

Drift, baselines and the maintenance nobody schedules

Most non-dispersive infrared CO2 sensors rely on automatic baseline correction, which assumes the sensor will periodically see air close to outdoor concentration, typically around 400 to 420 ppm. In an office that empties overnight, that assumption broadly holds. In a 24-hour gym, a hotel back-of-house corridor, or a venue running late licences through December, it may never see fresh air for weeks. The baseline creeps, and the readings drift quietly in one direction.

Electrochemical carbon monoxide cells have a finite service life, commonly two to three years, and an end-of-life flag that is easy to ignore when it appears in a submenu. Particulate sensors are sensitive to humidity, and readings taken above roughly 70 per cent relative humidity can be inflated by hygroscopic growth of the aerosol.

None of this is exotic. It is ordinary instrument maintenance, and it is the part of a monitoring programme most likely to be skipped.

From decoration to evidence

A dashboard is decorative when nobody can say where the box is, when it was last checked, or what the numbers mean at three in the morning. It becomes evidence when the supporting record is as carefully kept as the readings themselves.

That record needs, at minimum: the device identifier, its exact location described in words and on a plan, the mounting height, the logging interval, the calibration and maintenance history, and the date the sensor was last verified against a reference. It needs the awkward weeks as well as the good ones. Selective export is the fastest way to lose credibility.

Where readings are used to support a claim about ventilation performance, they should be read alongside occupancy, the state of the mechanical services, and the weather. A CO2 curve that peaks at 2,000 ppm every afternoon in a meeting room is a finding with a cause, and the cause is usually a damper, a fan setting or a closed door rather than a mystery.

A short placement protocol

Before the next monitor goes on the wall, it is worth agreeing four things: the height, the clearance from sources, the representative occupancy it is meant to reflect, and the person responsible for its annual check. Everything else, including the number of decimal places on the display, is downstream of those four decisions.

Get the position right and a modest sensor will earn its place in the building's evidence file. Get it wrong and no amount of resolution will rescue the reading.

All Articles

Related Articles

The Care Home Airflow File: Evidence That Outlasts a CO2 Reading

The Care Home Airflow File: Evidence That Outlasts a CO2 Reading

When the Number Looks Fine: CO2 Monitoring and the Discipline of Ventilation

When the Number Looks Fine: CO2 Monitoring and the Discipline of Ventilation

Before the First Christmas Booking: Five Airflow Checks for UK Licensed Premises

Before the First Christmas Booking: Five Airflow Checks for UK Licensed Premises